Using the pipe cutter only, neatly and accurately cut out desired
length of pipe for insertion of proper fitting. Remove both hub and
bell ends, or other compression couplings from wye branch fitting
to allow the wye branch to be inserted with no more than a total of
1/2 inch gap. Use band seal couplings, or similar couplings, and shear
rings and clamps to fasten the inserted fitting and hold it firmly
in place. The entire section shall then be encased in concrete having
a minimum thickness of four inches and extending eight inches beyond
each joint.
If another method is desired, a detail shall be submitted for
review and approval by the Village before the connection is made.
Indiscriminate breaking of the sewer main pipe is not allowed.
|
On-site inspection. After the wye branch has been inserted and
jointed, and before any additional fittings have been placed in the
service line, the installation shall be approved by the Superintendent,
or his authorized representative. After approval is granted the contractor
shall encase the work area as specified herein.
|
Backfill. To be placed in accordance with the Standard Specifications
for Water and Sewer Main Construction in Illinois, current edition.
In addition, any building sewers crossing any street, or traveled
alley shall be backfilled with granular backfill material.
|
Concrete encasement. When a riser is constructed and its height
is four feet or more measured from the flowline of the sewer main
to the top of the riser pipe, the wye connection shall be encased
in concrete to a height of at least one foot six inches above the
flowline of the sewer main. When the height of the riser is less than
four feet above the flowline of the sewer main, the wye connection
shall be backfilled to the top of the riser pipe with carefully placed
and compacted granular backfill.
|